4.2.3.

Pressure mode control parameters

There are three control parameters which can be modified to improve pressure mode performance: pressure

sensitivity, pressure time-out, and pressure gain.

CONTROL

PARAMETER

DESCRIPTION

DEFAULT

SECTION

Pressure sensitivity

Controls how much difference between the target pressure
and actual pressure that is allowed before the SENTRY
actively adjusts the engine speed to bring the discharge
pressure back to the target pressure.

6 PSI

6.5.2

Pressure time-out

The engine speed will be commanded to the idle RPM when
the discharge pressure drops below 30 PSI (and only after
the discharge pressure had been above 50 PSI) for the
number of seconds configured. The alarm will sound and the
OPERATOR CMD warning will be shown in the display
window (see section 5).

3 Seconds

6.6.8

Pressure gain

The pressure change requested with each Twister control
click in the INCREASE or DECREASE direction.

3 PSI

6.6.10