6.3. INFO menu

The User Info/Command Menu allows viewing of the Engine Hours, Pump Hours, and
Auxiliary Hours.

DISPLAY ITEM

FORMAT

SOURCE

Engine hours

XX.XX h

SAE J1939 CAN message – PGN 65253

Pump hours

XX.XX h

Internal timer, running with pump engaged
interlock

Auxiliary hours

XX.XX h

Internal timer, always running


This menu also allows resetting of the pump and auxiliary hours, zero calibrating the
pressure sensors, setting the factory defaults, and auto scaling the analog output (for
analog control method).

Use the soft buttons to navigate and execute options.

6.3.1.

Reset the Pump Hours

Enter the INFO menu and select “Reset Pump Hours” then press the SAVE button. The display will prompt you to
verify that you want to reset the pump hours. Press the green accept button to reset or the red cancel button to not
reset. Once back to the INFO menu you must press the SAVE button to save the reset operation and exit the
menu.

6.3.2.

Reset the Auxiliary Hours

Enter the INFO menu and select “Reset Auxiliary Hours” then press the SAVE button. The display will prompt you
to verify that you want to reset the auxiliary hours. Press the green accept button to reset or the red cancel button
to not reset. Once back to the INFO menu you must press the SAVE button to save the reset operation and exit
the menu.

6.3.3.

Zero Calibrate the pressure sensors

Enter the INFO menu and select “Zero Cal Pres Sensors” then press the SAVE button. The display will prompt you
to verify that you want to zero the pressure sensors. Press the green ACCEPT button to reset or the red CANCEL
button to not reset. Once back to the INFO menu you must press the SAVE button to save the zero calibration
operation and exit the menu.

6.3.4.

Set Factory Defaults

Enter the INFO menu and select “Set Factory Defaults” then press the SAVE button. The display will prompt you to
verify that you want to set the factory defaults. Press the green accept button to reset or the red cancel button to
not reset. Once back to the INFO menu you must press the SAVE button to save the factory default operation and
exit the menu.