FORM-ENG-0018 REV A 05-27-03

607 NW 27th Ave

Ocala, FL 34475

Ph: 352-629-5020 or 1-800-533-3569

Fax : 352-629-2902 or 1-800-520-3473

TECHNICAL DATA SHEET

PAGE

17

OF 36

DATE

6/19/2014

PRODUCT GROUP

THROTTLE CONTROL

P/N

3045-101-00-CL1, 3045-102-00-CL1

REV

1.02

PRODUCT

SENTRY PRESSURE GOVERNOR

BY

AMS


MESSAGE

DESCRIPTION

SENTRY RESPONSE

OPERATOR ACTION

CRITICAL: Sentry

In Standby.

Check Water

Source

Pump discharge pressure has
been less than 30 PSI for longer
than the configured pressure
time-out
.

SENTRY reduces engine speed
to the idle RPM and returns to
IDLE mode operation.

Operator should verify water
supply and then re-enable
PRESSURE mode operation.

Unable to

maintain

discharge

pressure

The SENTRY has increased the
engine speed more than 300
RPM above the stasis RPM.

SENTRY maintains the engine
speed at the stasis RPM + 300.

Operator should verify water
supply to determine why the
desired discharge pressure
cannot be maintained.

Discharge

Pressure Has

Increased More

Than 50 PSI Since

Setting RPMs

The SENTRY is in THROTTLE
mode and the discharge pressure
has increased more than 50 PSI
over the previous stasis pressure.

SENTRY maintains THROTTLE
mode operation but limits the
engine RPM to maintain no
more than a 50 PSI differential
over the pressure detected
when the operator set the
desired engine RPM.

No operator action required.
Operator may continue to use
SENTRY in THROTTLE mode.

5 volt reference

error

The SENTRY is not detecting the
5 volt supply voltage required for
analog control (pin 1, connector
C).

The SENTRY will not be able to
create the variable voltage
required for analog control
mode.

Operator should have the
SENTRY wiring confirmed.

Water Pressure >

10 PSI and Preset

Inhibit Enabled

The SENTRY has been
configured for RPM Preset inhibit.
The operator has pressed the
RPM preset button when 10 or
more PSI of discharge pressure
is detected.

The SENTRY will not increase
engine speed to the preset
RPM.

Operator should determine why
discharge pressure is detected
on the discharge side of the
pump.

Preset Is Not

Permitted With

Discharge PSI

Less Than 30

The SENTRY detects less than
30 PSI of discharge pressure.

The Sentry will not allow preset
operation

The operator should manually
adjust discharge pressure to
above 30 PSI and then use the
desired preset.

Intake pressure is

too low for

POSITIVE

pressure

operation

The SENTRY had determined
that the pump was operating with
positive intake pressure and
currently the intake pressure is
below the configured threshold.

No change in operation.

Operator should verify the intake
pressure to ensure proper
pumping operation.