EXM UHP– Installation Instructions

(Step 2 – Configure the System)

11
















































Under the Monitor Settings tab, enter the serial
number of the monitor being configured. This
number can be found on the monitor control box.

In the drop down menu, the monitor type can be
selected.

3 4

5

6

When using CAN communication within the EXM
system, 2 and only 2 components must be terminated
to ensure proper communication along the CAN line. .
If there have been no physical termination points
installed within your system, two termination points
must be selected during configuration.


Here is the first opportunity to terminate any of the
CAN operated EXM components in your system.

To maximize the efficiency of communication in your
CAN network, the two components to be terminated
should be at the extreme ends of your CAN line.

At the bottom of the Monitor Settings tab, default
settings regarding the Speed and Range of rotation of
your EXM monitor can be set.

Motor speeds can be changed after system
configuration is complete, if desired.

Travel amounts may be decreased after system
configuration but may not be increased further than
what is set as default during system configuration.