Installation Instructions -


In this section, the reader will be guided through the steps listed in the installation overview below. The
installation of the reader’s specific

EXM system may not require all of the instructions

included in this manual.













Please keep in mind the following wiring recommendations when mounting and wiring the

EXM system components.


Recommended electrical requirements for

EXM monitor:

 Power and Ground wire gauge and length: Distance (Ft) Wire Gauge (AWG)

100 - 150 8
50 < 100 10
25 < 50 14

< 25 16
 Power and Ground wire type: Cross Link or equivalent (Must meet or exceed NFPA 1901 Section 13)
 Maximum monitor amperage draw: 20 AMPS
 CAN wire gauge and length: Any length – 18-22 AWG
 CAN wire type and shielding: Twisted shielded pair - 105°C 150V (Belden 9841 series or equivalent)

o Shield Drain: Connect shield/drain to pin C of J1939 connector


Recommended electrical requirements for the 7000 series input devices:

 Power and Ground wire gauge and length: Any length - 22 AWG 105°C 150V
 Maximum input controller amperage draw: 500mA
 CAN wire gauge and length: Any length – 18-22 AWG
 CAN wire type and shielding: Twisted shielded pair - 105°C 150V (Belden 9841 series or equivalent)

o Shield Drain: Connect shield/drain to pin C of J1939 connector

 Docking station wire gauge type: 22 AWG cross link or equivalent

Installation Overview:

Step 1 – Mount and Wire All System Components (Pages 7)

Step 2 – Configure the EXM System (Pages 10)

Step 3 – Calibrate the EXM System (Pages 14)

Step 4 – Check Installation (Page 15)