Caution – Elkhart Brass Sidewinder 7161 EXM UHP User Manual
Page 15
EXM UHP– Installation Instructions
(Calibrate the EXM System)
15
o Press and hold PRESET and then press either the LEFT or RIGHT button. (On the joystick, hold
PRESET and move the stick to the right or left and release)
o The status LED on the monitor should blink then turn solid.
o Release the PRESET and either the LEFT or RIGHT button. The horizontal axis is now calibrated.
Calibrating Vertical Rotation - The Vertical zero (0˚) position is factory set, however you may still set a
new vertical zero point. This calibration will establish the highest vertical travel point of the monitor and
allow rotation in the downward direction the total range specified during system calibration. This differs
from the horizontal rotation calibration where the zero point is in the middle of the rotation range.
o Using RIGHT, LEFT, UP, and DOWN buttons, position the monitor such that it is aimed directly
vertical or at the uppermost limit of travel specified during system configuration.
o Press and hold PRESET and then press the UP button. (On the joystick, hold PRESET and move the
stick up and release)
o The status LED on the monitor should blink then turn solid.
o Release the PRESET and UP buttons. The vertical axis is now calibrated.
o Exit Setup Mode and check the monitor’s rotation limits. The monitor should not hit itself or other
objects. Recalibrate the EXM system if needed.
Caution:
If the vertical zero point is set too far forward, the monitor may be allowed to
crash into itself at the lower points of vertical travel. Be careful not to move the monitor into
obstructions or itself as this will cause the monitor motors to over current. The monitor may
need to be moved in reverse, manually, if this occurs.
Installation Step 4: Check Installation
After mounting, wiring, configuring, and calibrating the
EXM system, check the
installation of the entire EXM system.
Ensure that all components have been mounted securely and have had the correct fuses installed within
their wiring leads.
Ensure that all components have been configured and that all components are functioning.
Ensure that the
EXM system has been calibrated correctly for its specific installation.
Ensure that all components are performing normally.
o For a list of operating functions that the
EXM system should be capable of
performing, go to the operating instructions section on page 16.