Electrical installation, Wiring el 1xx can/plc/mpi, Can interface – Lenze HMI for visualisation / with control technology User Manual

Page 32: Only connect terminals of the same signal type

Advertising
background image

Electrical installation

Wiring
EL 1xx CAN/PLC/MPI

6

l

32

LDCDS−EL100 EN 9.0

CAN interface

)

Note!

ƒ

Only connect terminals of the same signal type.

ƒ

For further information with regard to the CAN bus system please refer to
the CAN Communication Manual.

CG

CAN

LO HI

CG

CAN

LO HI

CG

CAN

LO HI

R

R

A

n

A

2

A

1

EL100−009

A1

Node 1

A2

Node 2

An

Node n

CG

CAN−GND

LO

CAN−LOW

HI

CAN−HIGH

R

120

W−bus terminating resistor

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m

Description

Connection type

Cable type

6

1

CAN bus connection
Pin 1: Not assigned
Pin 2: CAN−LOW (LO)
Pin 3: CAN−GND (CG)
Pin 4 ... 6: Not assigned
Pin 7: CAN−HIGH (HI)
Pin 8 ... 9: Not assigned

9−pole Sub−D plug

CAN cable acc. to ISO 11898−2

with 9−pole Sub−D socket

IPC001

Advertising