Electrical installation, Wiring el 1xx eco (plc), Usb interface – Lenze HMI for visualisation / with control technology User Manual

Page 35: Can interface, Only connect terminals of the same signal type

Advertising
background image

Electrical installation

Wiring

EL 1xx ECO (PLC)

6

l

35

LDCDS−EL100 EN 9.0

USB interface

Description

Connection type

Cable type

USB 2.0 host connection
Max. load: 5 V/500 mA

USB−A socket

USB cable with USB−A plug

IPC001

CAN interface

)

Note!

ƒ

Only connect terminals of the same signal type.

ƒ

For further information with regard to the CAN bus system please refer to
the CAN Communication Manual.

CG

CAN

LO HI

CG

CAN

LO HI

CG

CAN

LO HI

R

R

A

n

A

2

A

1

EL100−009

A1

Node 1

A2

Node 2

An

Node n

CG

CAN−GND

LO

CAN−LOW

HI

CAN−HIGH

R

120

W−bus terminating resistor

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m

Advertising