SATEC PM296 User Manual

Page 10

Advertising
background image

Chapter 1 Introduction

2

Remote Display Module - Optional

The RPM096 can be equipped with a Remote Display Module (RDM096) that
provides local data display as well as setup capabilities. The RDM096 is
connected to the RPM096 via a conventional DB15 connector (0.4/1.8/3.0 m
cable supplied).

The display is multi-page and is composed of three windows with high-brightness
digital LEDs.

One

galvanically isolated direct current voltage input with options 300V, 100V

or 20V.

3 voltage

and 4 current galvanically isolated inputs for direct connection to

power line or via potential and current transformers.

Setup

is menu driven, with optional password protection.

Two communication ports

are available for RS-232/RS-485 and RS-422/RS-

485 standards, with ASCII, Modbus and DNP3.0 protocols. In ASCII and Modbus
protocols, 120 assignable registers allow the user to re-map either register
address accessible in the instrument to the user assignable register area.
Changing setups and resetting accumulated data through communications can be
secured by the password.

6 relays

are provided for energy pulsing (KYZ) or alarm and remote control.

12 optically isolated status inputs

are provided for status monitoring with

timestamp and for external demand and time synchronization.

Two optically isolated analog outputs

with an internal power supply are

provided for remote monitoring or control. Current loop options are 0-20mA, 4-
20mA, 0-1mA,

± 1mA.

Real Time Clock

is provided in the PM296/RPM096E for date and time stamp

log and demand interval synchronization. Standard or Daylight Savings Time
(DST) with automatic time adjustment is available. DST switch dates can be
configured for the use in different time zones.

The TOU (Time of Use) system:

• up to 16 TOU energy register groups, each of which can be allocated to accumulate

kWh (import and export), kvarh (import and export), kVAh and energy from 12 external
meters through 12 pulse inputs

• up to 3 TOU Maximum Demand register groups, each of which can be allocated to

record maximum kW import and export, kvar import and export, or kVA demand

• sliding window and thermal maximum demand options

• up to 16 tariff energy registers (counters) per group

• up to 16 tariff Maximum Demand registers per group
• up to 16 daily profiles (e.g., 4 seasons, 4 daily profiles per season)

• up to 8 daily start times (tariff changes)

• 2 calendars
• automatically configurable daily and monthly TOU profile log for each allocated energy

and maximum demand register using season energy tariffs