Reset menu, Electrical installation, 13 reset menu – SATEC PM296 User Manual

Page 47

Advertising
background image

Chapter 4 Setup Menus

39

4.13 Reset Menu

This menu allows you to reset to zero the accumulators and Min/Max registers in
your instrument. The menu can be only accessed via the Setup Change Menu
(CHG)

. If the reset is disabled from the Basic Setup Menu (see Section 4.1), you

will not be able to enter this menu.

The following designations are used in the menu to specify a data location to be
reset:

A.dnd

Resets volt/ampere maximum demands

P.dnd

Resets total power maximum demands

dnd

Resets all total maximum demands

EnrG

Resets total energies

Lo.Hi

Resets Min/Max registers (does not affect maximum demands)

tOU.E

Resets the TOU energy registers

tOU.d

Resets the TOU maximum demand registers

Cnt

Resets all pulse counters

Cnt.1 -
Cn.16

Resets counter # 1- #16

To reset the desired locations:

Press to activate the middle window, and then use the up/down arrow keys to

scroll to the desired data location entry.





Press to activate the lower window.
Press and hold for about 5 seconds until the do label is replaced with done,

and then release the key. You will return to the middle window.

To quit the reset menu:

Press .

NOTE

If changing data in the instrument via the front panel is not secured by a password, the fast
reset of the Min/Max registers, maximum demands and total energies can be made from the
data display mode (see Section 5.1) and counters from the Status Information Menu (see
Section 6.1) without entering the reset menu.

rSt

do

EnrG

SELECT

ESC

ENTER

SELECT

SELECT

CHG

rSt

ENTER

ENTER

Advertising