3

Waveform Recorder

for waveform capture and logging on different events.

Along with the disturbance monitor it allows for capture and recording of various
types of disturbances with a duration from one millisecond and up to tens
seconds - transients, outages, sags, surges and deviations in voltage level.

Event and data logging

on different events with real time clock and 1-Mbyte

non-volatile memory:

• instrument switch on/off

• instrument setup change
• external status change

• event/alarm setpoints operations

• clock update

Each event record stores: date and time stamp, event name, log value (after
alarm setup operation) and effect (operation or release).

Data logging

is used for: load profile logging (at 5,15 or 30 minute intervals),

TOU energy counters logging and data logging after alarm setup operation or
new state of digital status input.

Calculation of memory size is according to the following:

Log name

Number of bytes

in record

Number of daily/

monthly records

Number of

days/months

Memory size

(bytes)

Event log

14

NR (up to 10) daily

ND

14 * NR * ND

Load profile log

NB = 4 * NP+8 NR =1440/TI - daily

ND

NB * NR * ND

TOU energy log

NB = 4 * NP+8 NR = 1- monthly

NM

NB * NR * NM

Alarm data log

NB = 4 * NP+8

NR (up to 5) - daily ND

NB * NR * ND

Total memory

524288

Where:

NP = number of parameters in a record (up to 16) and 8 - number of bytes for timestamp;

TI = time interval between two records, minutes.

Example:

Event log

must store data up to 60 days (ND=60)

Load profile log

- up to 60 days and every record consist of NP=5 parameters: voltages per

phase, active and reactive powers integrated TI=5 minutes),

Monthly TOU energy log

- 60 months and every record consist of NP=10 parameters - 4

energy tariffs and 4 TOU Maximum Demand registers, Active and Reactive Energy
registers),

Alarm Data log -

60 days, every record consist of NP=13 parameters - 3 voltages, 3

currents, active, reactive and apparent powers, frequency, THD voltage of phases L1, L2
and L3,
Data logging requires the following memory:

Log name

Number of bytes
in one record

Number of
daily/monthly
records

Number of days
(months)

Memory
size, in
bytes

Event log

14

10

60

8400

Load profile log

4 * 5+8 =28

1440/5= 288

60

483840

TOU energy log

4 * 10+8 = 48 1

60

2880

Alarm data log

4 * 13+8 = 60

5

60

18000

Required memory

513120