Measurement specifications, User selectable options menu – SATEC PM296 User Manual

Page 74

Advertising
background image

Appendix: Technical Specifications

66

Measurement Specifications

Parameter

Full scale

Accuracy, %

Range

Display resolution (%Rdg)

@

input

Rdg

FS

Conditions

@ range

120VxPT
@ 120V
400VxPT
@ 690V

For L-N reading
and 3OP2/3OP3
wiring

modes

Voltage

208VxPT
@ 120V
690VxPT
@ 690V

For L-L reading
except
3OP2/3OP3

wiring modes

0.1 0.11 10% to 120% FS 0 to 999,000 V

Direct wiring (PT=1):
0.1 V @ 0.1V to 999.9 V
Wiring via PTs (PT>1):
0.001 kV @ 0.001kV to 9.999 kV
≤0.1% @ 10.00 kV to 999.0 kV
Starting voltage 1.5% FS

Line current

CT PRIMARY CURRENT 0.2 0.007 1% to 200% FS

0 to 9999 A

0.01 A @ 0.01A to 99.99 A
≤0.1% @ 100.0 A to 9999 A
Starting current 0.5% FS

Active power

0.36

×

PT

×

CT @ 120V

1.2

×

PT

×

CT @ 690V


0.3


0.002
0.002

|PF|

≥ 0.5 and

or

-2,000,000 to
+2,000,000 kW

Direct wiring (PT=1):
0.001 kW @ 0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW @ 0.001MW to 9.999 MW
≤0.1% @ 10.00 MW to 2000 MW

Reactive power

0.36

×

PT

×

CT @ 120V

1.2

×

PT

×

CT @ 690V


0.38


0.002
0.002

|PF|

≤ 0.9 and

or

-2,000,000 to
+2,000,000 kvar

Direct wiring (PT=1):
0.001 kvar @ 0.001kvar to 9.999 kvar
Wiring via PTs (PT>1):
0.001 Mvar @ 0.001Mvar to 9.999 Mvar
≤0.1% @ 10.00 Mvar to 2000 Mvar

Apparent power 0.36

×

PT

×

CT @ 120V

1.2

×

PT

×

CT @ 690V


0.3


0.002
0.002

|PF|

≥ 0.5 and

or

0 to 2,000,000 kVA

Direct wiring (PT=1):
0.001 kVA @ 0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA @ 0.001MVA to 9.999 MVA
≤0.1% @ 10.00 MVA to 2000 MVA

Power factor

1

0.35 |PF|

≥ 0.5,

≥ 2% FSI

-0.999 to +1.000

0.001

Frequency

0.02

45.00 to 65.00 Hz

0.01 Hz

Neutral
(unbalanced)

t

CT PRIMARY CURRENT 0.3 0.01 1% to 200% FS

0 to 9999 A

0.01 A @ 0.01A to 99.99 A
≤0.1% @ 100.0 A to 9999 A

0.3 + 0.5 x
(1-U/U

FS

)

0.38 + 0.6 x
(1-U/U

FS

)

0.3 + 0.5 x
(1-U/U

FS

)