Chapter 4 Setup Menus

32

4.8 Timers Setup Menu

This menu allows you to access the four interval timers provided by the
PM296/RPM096

which can trigger setpoints on a user-defined time interval basis.

This is useful for continuous data logging at specified time intervals in order to
produce trend and load profile graphs.

Each timer has a time interval range up to 9999 seconds at a one-second resolution and
runs independently. The timer accuracy is about

±0.05 sec. To use a timer as the trigger for

a setpoint, simply select one of timers as a trigger when defining the setpoint, and then
specify for the selected timer a non-zero time interval at which you want the periodic action
(for example, a data log) to be made. To stop a timer, set the time interval to zero. Each
timer can be used to trigger multiple setpoints, for example, if you need multiple data logs at
the same time.


Timer setup

To select a timer:

Press to activate the middle window, and then use the

up/down arrow keys to scroll to the desired timer. The time interval
associated with the timer is displayed in the lower window.

To change the timer interval:

Press to activate the lower window.
Use the up/down arrow keys to set the desired time interval. The

available range is 0-9999 (seconds). Setting the interval to zero stops
the timer.

Press to store your new setting.
Press to leave the timer setup unchanged.

To quit the timer setup menu:

Press .