Chapter 4 Setup Menus

31

4.7 Pulsing Output Setup Menu

This menu allows you to program either of the six relays provided by your
PM296/RPM096

instrument to output energy pulses. Available pulsing

parameters are listed in Table 4-5.

To select a pulse relay:

Use the up/down arrow keys to scroll to the desired relay. The pulsing

parameter assigned to the relay is displayed in the middle window, and
the amount of unit-hours per pulse is displayed in the lower window.

To change the pulse relay setup:

Press to activate the middle window.

Use the up/down arrow keys to scroll to the desired output parameter.

Selecting nonE disables pulsing through this relay.

Press to activate the lower window.
Use the up/down arrow keys to set the amount of unit-hours per pulse.

The available range is 1-9999.

Press to store the new setup, or press to quit the setup

without changes.

To quit the pulsing setup menu:

From the upper window, press or .

Table 4-5 Pulsing Output Parameters

Code Parameter
nonE Output

disabled

Ac.Ei

kWh import (positive)

Ac.EE

kWh export (negative)

Ac.Et

kWh total (absolute)

rE.Ei

kvarh import (inductive)

rE.EE

kvarh export (capacitive)

rE.Et

kvarh total (absolute)

AP.Et

kVAh total


NOTES

1. You will not be able to store your setup in the instrument if you assigned a parameter to

relay output with a zero number of unit-hours per pulse, or if the parameter you selected
has just been assigned to another relay output.

2. If a relay you allocated for pulsing has been manually operated or released, it reverts

automatically to normal operation.

3. If a relay you allocated for pulsing has been engaged by an alarm/event setpoint, the

setpoint is automatically disabled.