Chapter 4 Setup Menus

21

Table 4-1 Basic Setup Options

(

∗ default setting

)

Code Parameter Options Description

ConF

Wiring mode

3OP2

3-wire open delta using 2 CTs
(2 element)

4Ln3

4-wire Wye using 3 PTs (3 element), line to
neutral voltage readings

3dir2

3-wire direct connection using 2 CTs (2
element)

4LL3

4-wire Wye using 3 PTs (3 element), line to
line voltage readings

3OP3

3-wire open delta using 3 CTs
(2½ element)

3Ln3

4-wire Wye using 2 PTs (2½ element), line to
neutral voltage readings

3LL3

4-wire Wye using 2 PTs (2½ element), line to
line voltage readings

Pt

PT ratio

1.0

-

6,500.0

The phase potential transformer ratio

Ct

CT primary current

1-5000A
(5

∗)

The primary rating of the phase current
transformer

Ct.Au

Auxiliary CT primary
current

1-5000A/mA
(5000

∗)

The primary rating of the auxiliary current
transformer

dc.OF DC voltage zero

offset

0-9999 (0

∗) The reading of the DC voltage corresponding

to a zero DC voltage input

dc.FS DC voltage full scale

reading

0-9999 (20,
100, 300

∗)

The reading of the DC voltage corresponding
to a full-scale DC voltage input. By default it is
set to the DC full-scale input (20, 100 or 300
VDC)

d.P

Demand period

1, 2, 5, 10,
15

, 20, 30,

60, E

The length of the demand interval (sub-interval
for sliding window demand) for power demand
calculations, in minutes. E = external
synchronization

n.dp

Number of demand
periods

1-15
(1

∗)

The number of demand sub-intervals to be
averaged for sliding window demands. A
product of the demand period and the number
of demand periods should not exceed 60 min.
For block demand, set this value to one.

A.dP

Ampere/Volt
demand period

0-1800s
(900

∗)

The length of the demand period for
volt/ampere demand calculations, in seconds
0 = measuring peak current

t.con Thermal demand

time constant

1-3600.0 s
(195.4

∗)

The simulated thermal element time constant
for thermal demand measurements

buF

Averaging buffer
size

8

,16,32

The number of measurements for RMS sliding
averaging

rSt

Reset enable/disable diS, En

Protects all reset functions, both via the front
panel or communications.

PrE.C

The number of pre-
event cycles for the
waveform recorder

1-8 (1*)

The number of waveform cycles to be recorded
before the event that triggered waveform
capture