Ions, Display setup menu, Appendix: technical specifications – SATEC PM296 User Manual

Page 71: Input and output ratings

Advertising
background image

Appendix: Technical Specifications

63

Appendix: Technical Specifications

8. ions

Input and Output Ratings

CATEGORY

II

POLLUTION DEGREE

2

(IEC 664)

120 V AC INPUT USING PT (up to 120+20% V line-to-line voltage)

Burden: < 0.15 VA

3 galvanically
isolated current
inputs

CATEGORY

II

690 V AC

DIRECT INPUT (up to 690+15% V line-to-line voltage or
up to 500 V line-to-neutral voltage)
Burden: < 0.35 VA
INPUT USING PT (up to 120+20% V line-to-line voltage)
Burden: < 0.03 VA

POLLUTION DEGREE

2

(IEC 664)

1 A

INPUT via CT with 1 A secondary output
Burden: < 0.15 VA
Overload withstand: 2 A RMS continuous, 50 A RMS for
1 second

1 galvanically
isolated auxiliary
current input - I

4

CATEGORY

II

5 A

INPUT via CT with 5 A secondary output
Burden: < 0.15 VA
Overload withstand: 10 A RMS continuous,
250 A RMS for 1 second

POLLUTION DEGREE

2

(IEC 664)

1 A

INPUT via CT with 1 A secondary output
Burden: < 0.15 VA
Overload withstand: 2 A RMS continuous, 50 A RMS for
1 second

CATEGORY

II

POLLUTION DEGREE

2

(IEC 664)

5 A

INPUT via CT with 5 A secondary output
Burden: < 0.15 VA
Overload withstand: 10 A RMS continuous, 250 A RMS
for 1 second

1 galvanically
isolated direct
current voltage
input


300 V DC
100 V DC
20 V DC

CATEGORY

II

,

POLLUTION DEGREE

2

(IEC 664)

Burden: 0.4 W
Burden: 0.15 W
Burden: 0.005 W

Digital inputs

12 optically isolated, dry contact sensing inputs (voltage-free)

Relay outputs

5 relays rated at 5A, 250 VAC/30 VDC, 2 contacts (SPST Form A)
1 relay rated at 5A, 250 VAC/30 VDC, 3 contacts (SPDT Form C)

2 optically isolated
analog outputs

0(4)-20 mA
±1 mA
0-1 mA

Accuracy: 0.5%, Non-linearity:

±100 µA

Maximum load: 510

Maximum load: 10K

Maximum load: 10K

Advertising