Chapter 4: Zone Programming

31

CHAPTER 4: ZONE PROGRAMMING

This chapter explains the keyboard commands for the monitoring
functions of the 1800. This includes:

Configure Zone Type
Enable/disable Zones
Temperature Scale
Table Range for 4-20mA sensors
Alarm Recognition Time
Alarm Limits
Zone Calibration
AC Power Monitoring Enable/disable
AC Power Recognition Time
Sound Level Monitoring Enable/disable
Sound Level Recognition Time
Sound Level Calibration

CONFIGURE ZONE TYPE

The 1800 is compatible with normally open, normally closed,
10K thermistor (temperature), 2.8K thermistor (temperature),
and 4–20mA type sensors. All of the Zones are configured
simultaneously by keying in a simple key sequence after connecting
all of your sensors. Make sure all sensors are in their normal state.
All 4–20mA transducers should be powered on.

NOTE: Temperature sensors will default configure

to 2.8K. If you are connecting any 10K sensors to

the 1800, these must be configured manually. (See

the Manual Configuration section)

To configure the Zone Types:

1. Press the SET key.