Installation, Clearances – Regency Bellavista B36XT Medium Gas Fireplace User Manual

Page 10

Advertising
background image

10

Regency Bellavista™ B36XT Gas Fireplace

INSTALLATION

Alcove

Caution Requirements

The top, back and sides of the fi replace are defi ned by

standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials are not

adhered to. It is of greatest importance that this fi replace and vent

system be installed only in accordance with these instructions.

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fi replace and vent system be installed only in accordance with these instructions.

B36XT Clearance Requirements

Minimum Vent Clearances

to Combustibles

Clearance:

Dimension

Measured From:

A: Mantel Height (min.)

13" (330mm)

Top of Fireplace Opening

B: Sidewall

12" (304mm) one side

only

Side of Fireplace Opening

C: Ceiling

36-3/4" (933mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12" (304mm)

21 " (533mm) from
Top of Fireplace Opening

E: Alcove Width

84" (2134mm)

Wall to Wall (Minimum)

F: Alcove Depth

36" (914mm)

Front to Back Wall (Maximum)

Notes:

0"

No Hearth Required

Horizontal Top

2" (51mm)

Horizontal Side

1-1/2 " (38mm)

Horizontal Bottom

1-1/2" (38mm)

Vertical Vent

1-1/2" (38mm)

E

F

Advertising