Regency Bellavista™ B36XT Gas Fireplace

25

INSTALLATION

HORIZONTAL TERMINATIONS

FLEX VENT 5" X 8"

These venting systems, in combination with the B36XT Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.

Regency

®

Direct Vent (Flex) System 4 foot Termination Kit (Part# 946-615) includes all the parts needed to install the B36XT with a either a

top or rear vent.

Note: If top venting this unit, the 5" x 8" venting may only be used if venting to the minimum of 42-1/3" to centerline.
No other application is approved.

1) 8"

dia.

fl exible liner (4 ft. length)

2) 5"

dia.

fl exible liner (4 ft. length)

3) spring spacers (4)
4) thimble
5) AstroCapXL termination cap (1)
6) screws

(12)

7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point,

Stainless Steel (4)

10) vinyl siding standoff

Notes:

1) Liner sections should be continuous without any joints or seams.

2) Only Flex pipe purchased from Regency may be used for Flex installations.

3) Regency

®

Direct Vent System (Flex) is only approved for horizontal terminations.

Note: If longer runs are required - rigid pipe must be used.

FPI Kit #

Length Contains:

#946-615

4 Feet

1) 8”

fl exible liner (Kit length)

2) 5”

fl exible liner (Kit length)

3) spring

spacers

4) thimble
5)

AstroCap termination cap

6) screws
7)

tube of Mill Pac

8) plated

screws

9)

S.S. screws #8 x 1-1/2” drill point

10) vinyl siding standoff