Installation, Venting arrangements for horizontal terminations – Regency Bellavista B36XT Medium Gas Fireplace User Manual

Page 24

Advertising
background image

24

Regency Bellavista™ B36XT Gas Fireplace

INSTALLATION

The diagrams show all allowable combinations of vent runs with 5" x 8" venting using the Regency direct vent system or rigid vent system.
A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent length of 3ft (0.9m).

Note: Must use optional rigid pipe adaptor (Part # 770-994) when using Rigid Pipe vent systems.

• Maintain clearance to combustibles.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.

2

0

12

6

4

8

10

2

0

6

4

8

V

ertical

Height

(Feet)

Rigid

44-1/4"(1.1m)

Horizontal (Feet)

Max. 36”(0.9m)

Flex

42-1/8"(1.0m)

Factory Setting - No Restrictor Required

Factory Setting - No Restrictor Required

VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS

FLEX VENT OR RIGID PIPE 5" X 8"