PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-11

Control I/O Terminal Designations

No. Signal

Default

Description

Param.

01

Stop

(1)

/

Function Loss

Coast

Factory installed jumper or a normally closed input must
be present for the drive to start.
Program with P036 [Start Source].

P036

(1)

02

Start/Run FWD

HAND Mode: Command comes from Integral Keypad.
AUTO Mode: I/O Terminal 02 is active.
Program with P036 [Start Source].

P036, P037

03

Direction/Run REV

Rev Disabled

To enable reverse operation, program with A166
[Reverse Disable].
Program with P036 [Start Source].

P036, P037,
A166

04

Digital Common

For digital inputs. Tied to I/O Terminal 09.
Electronically isolated with digital inputs from analog I/O
and opto output.

05

Digital Input 1

Purge

(2)

Program with T051 [Digital In1 Sel].

T051

06

Digital Input 2

Local

Program with T052 [Digital In2 Sel].

T052

07

Digital Input 3

Clear Fault

Program with T053 [Digital In3 Sel].

T053

08

Digital Input 4

Comm Port

Program with T054 [Digital In4 Sel].

T054

09

Digital Common

For digital inputs. Tied to I/O Terminal 04.
Electronically isolated with digital inputs from analog I/O
and opto output.

10

Opto Common

For opto-coupled outputs. Electronically isolated with
opto output from analog I/O and digital inputs.

11

+24V DC

Drive supplied power for digital inputs.
Referenced to Digital Common. Max. Output: 100mA.

12

+10V DC

Drive supplied power for 0-10V external potentiometer.
Referenced to Analog Common. Max. Output: 15mA.

P038

13

Analog Input 1

0-10V

External 0-10V (unipolar), 0-20mA or 4-20mA input
supply or potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI1 DIP Switch to 20mA.
Program with T069 [Analog In 1 Sel].
Input Impedance:

100k ohm (Voltage Mode)
250 ohm (Current Mode)

T069, T070,
T071, T072

14

Analog Common 1

Common for Analog Input 1 and Analog Output 1 and 2.
Electrically isolated from digital I/O and opto output.

15

Analog Output 1

OutFreq 0-10

Default analog output is 0-10V.
For current (mA) value, set AO1 DIP Switch to 20mA.
Program with T082 [Analog Out1 Sel].
Maximum Load:

4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)

P038,
T051-T054,
A152

16

Analog Output 2

OutCurr 0-10

Default analog output is 0-10V.
For a current (mA) value, set AO2 DIP Switch to 20mA.
Program with T085 [Analog Out2 Sel].
Maximum Load:

4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)

T082, T084,
T085, T086,
T087

17

Analog Input 2

0-10V

Optically isolated external 0-10V (unipolar), ±10V
(bipolar), 0-20mA or 4-20mA input supply or
potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI2 DIP Switch to 20mA.
Program with T073 [Analog In 2 Sel].
Input Impedance: 100k ohm (Voltage Mode)

250 ohm (Current Mode)

T073, T074,
T075, T076

18

Analog Common 2

For Analog Input 2. Electronically isolated from digital I/O
and opto output. With Analog Input 2, provides one fully
isolated analog input channel.

19

Opto Output

At Frequency

Program with T065 [Opto Out Sel].

T065, T066,
T068

20

RS485 (DSI) Shield –

Terminal connected to Safety Ground - PE when using
the RS485 (DSI) Communication Port.

(1)

See Footnotes (1) and (4) on previous page.

(2)

See the User Manual for Important information regarding Stop commands and the [Digital Inx Sel] Purge option.