Communications group parameters, No. parameter min/max display/options default – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 21

Advertising
background image

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-21

T082
T085

[Analog Out1 Sel]
[Analog Out2 Sel]

0/20

1

0
1

T083
T086

[Analog Out1 High]
[Analog Out2 High]

0/800%

1%

100%

T084
T087

[Anlg Out1 Setpt]
[Anlg Out2 Setpt]

0.0/100.0%

0.1%

0.0%

T088 [Anlg Loss Delay]

0.0/20.0 Secs

0.1 Secs

0.0 Secs

No.

Parameter

Min/Max

Display/Options

Default

Setting

Output
Range

Min. Output
Value

Max. Output Value

Filter

DIP Switch
AO1

Related
Parameter

0 OutFreq 0-10

0-10V

0V = 0 Hz

[Maximum Frequency]

None

10V

b001

1 OutCurr 0-10

0-10V

0V = 0 Amps

200% Drive Rated FLA

Filter A

10V

b003

2 OutTorq 0-10

0-10V

0V = 0 Amps

200% Drive Rated FLA

Filter A

10V

b013

3 OutVolt 0-10

0-10V

0V = 0 Volts

120% Drive Rated Output V

None

10V

b004

4 OutPowr 0-10

0-10V

0V = 0 kW

200% Drive Rated Power

Filter A

10V

b010

5 Setpnt 0-10

0-10V

0V = 0.0%

100.0% Setting

None

10V

T084

6 TstData 0-10

0-10V

0V = 0000

65535 (Hex FFFF)

None

10V

A196

7 OutFreq 0-20

0-20 mA

0 mA = 0 Hz

[Maximum Frequency]

None

20 mA

b001

8 OutCurr 0-20

0-20 mA

0 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b003

9 OutTorq 0-20

0-20 mA

0 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b013

10 OutVolt 0-20

0-20 mA

0 mA = 0 Volts

120% Drive Rated Output V

None

20 mA

b004

11 OutPowr 0-20

0-20 mA

0 mA = 0 kW

200% Drive Rated Power

Filter A

20 mA

b010

12 Setpnt 0-20

0-20 mA

0 mA = 0.0%

100.0% Setting

None

20 mA

T084

13 TstData 0-20

0-20 mA

0 mA = 0000

65535 (Hex FFFF)

None

20 mA

A196

14 OutFreq 4-20

4-20 mA

4 mA = 0 Hz

[Maximum Frequency]

None

20 mA

b001

15 OutCurr 4-20

4-20 mA

4 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b003

16 OutTorq 4-20

4-20 mA

4 mA = 0 Amps

200% Drive Rated FLA

Filter A

20 mA

b013

17 OutVolt 4-20

4-20 mA

4 mA = 0 Volts

120% Drive Rated Output V

None

20 mA

b004

18 OutPowr 4-20

4-20 mA

4 mA = 0 kW

200% Drive Rated Power

Filter A

20 mA

b010

19 Setpnt 4-20

4-20 mA

4 mA = 0.0%

100.0% Setting

None

20 mA

T084

20 TstData 4-20

4-20 mA

4 mA = 0000

65535 (Hex FFFF)

None

20 mA

A196

T083 Setting

T082 Setting

T082 Max. Output Value

50%

1 “OutCurr 0-10”

5V for 200% Drive Rated Output Current

90%

11 “OutPowr 0-20”

18 mA for 200% Drive Rated Power

Communications Group Parameters

No.

Parameter

Min/Max

Display/Options

Default

C101 [Language]

1/10

1 = “English”
2 = “Français”
3 = “Español”
4 = “Italiano”
5 = “Deutsch”

6 = “Reserved”
7 = “Português”
8 = “Reserved”
9 = “Reserved”
10 = “Nederlands”

1

C102 [Comm Format]

0/9

0 = “RTU 8-N-1”
1 = “RTU 8-E-1”
2 = “RTU 8-O-1”
3 = “RTU 8-N-2”
4 = “RTU 8-E-2”

5 = “RTU 8-O-2”
6 = “MetaSys N2”
7 = “P1 8-N-1”
8 = “P1 8-E-1”
9 = “P1 8-O-1”

0

Power to drive must be cycled before any
changes will affect drive operation.

C103 [Comm Data Rate]

0/5

0 = “1200”
1 = “2400”
2 = “4800”

3 = “9600”
4 = “19.2K”
5 = “38.4K”

0

C104 [Comm Node Addr]

1/247

1

100

C105 [Comm Loss Action]

0/5

0 = “Fault”
1 = “Coast Stop”
2 = “Stop”

3 = “Continu Last”
4 = “Run Preset 0”
5 = “Kypd Inc/Dec”

0

C106 [Comm Loss Time]

0.1/60.0 Secs

0.1 Secs

5.0 Secs

C107 [Comm Write Mode]

0/1

0 = “Save”

1 = “RAM Only”

0

C108 [Start Source 2]

0/6

0 = “Keypad”
1 = “3-Wire”
2 = “2-Wire”

3 = “2-W Lvl Sens”
4 = “2-W Hi Speed”
5 = “Comm Port”
6 = “2-W Lvl/Enbl”

3

Sets the control scheme used to start the drive
when in Auto/Remote mode.

C109 [Speed Ref 2]

0/5

0 = “Drive Keypad”
1 = “InternalFreq”
2 = “Analog In 1”

3 = “Analog In 2”
4 = “Preset Freq”
5 = “Comm Port”

2

Advertising