PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-9

I/O Terminal Block Specifications

(2)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Refer to the PowerFlex 400 User Manual for maximum control cable
length recommendations.

I/O Wiring Recommendations

Wire Type(s)

Description

Minimum
Insulation Rating

Belden 8760/9460
(or equiv.)

0.8 mm

2

(18AWG), twisted pair, 100%

shield with drain.

(1)

(1)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

2

(18AWG), 3 conductor, shielded for

remote pot only.

Frame

Maximum Wire Size

(2)

Minimum Wire Size

(2)

Torque

C, D, E, F

1.3 mm

2

(16 AWG)

0.13 mm

2

(26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)