Specifications, fuses and circuit breakers – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 5

Advertising
background image

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-5

Specifications, Fuses and Circuit Breakers

Drive Ratings

Catalog
Number

Output Ratings Input Ratings

Branch Circuit Protection

Power
Dissipation

kW (HP)

Amps

Voltage

Range

kVA Amps

Fuses

(1)

140M Motor
Protectors

(2)

(3)

Contactors

Min.
Enclosure
Volume

(4)

(in.

3

)

IP20 Open

Watts

50°C

200 - 240V AC – 3-Phase Input, 0 - 230V 3-Phase Output

22C-B012N103 2.2 (3.0)

12

180-265 6.5

15.5

20

140M-F8E-C16 100-C23

5098

146

22C-B017N103 3.7 (5.0)

17.5

180-265 8.8

21

30

140M-F8E-C25 100-C37

5098

207

22C-B024N103 5.5 (7.5)

24

180-265 10.9 26.1

35

140M-F8E-C32 100-C37

5098

266

22C-B033N103 7.5 (10)

33

180-265 14.4 34.6

45

140M-F8E-C45 100-C45

5098

359

22C-B049A103 11 (15)

49

180-265 21.3 51

70

100-C60

488

22C-B065A103 15 (20)

65

180-265 28.3 68

90

100-C85

650

22C-B075A103 18.5 (25) 75

180-265 32.5 78

100

100-D95

734

22C-B090A103 22 (30)

81

180-265 38.3 92

125

100-D110

778

22C-B120A103 30 (40)

120

180-265 51.6 124

175

100-D180

1055

22C-B145A103 37 (50)

130

180-265 62.4 150

200

100-D180

1200

380 - 480V AC – 3-Phase

Input, 0 - 460V 3-Phase Output

22C-D6P0N103 2.2 (3.0)

6

340-528 6.3

7.5

10

140M-D8E-C10 100-C09

5098

105

22C-D010N103 4.0 (5.0)

10.5

340-528 10.9 13

20

140M-D8E-C16 100-C16

5098

171

22C-D012N103 5.5 (7.5)

12

340-528 11.9 14.2

20

140M-D8E-C16 100-C23

5098

200

22C-D017N103 7.5 (10)

17

340-528 15.3 18.4

25

140M-D8E-C20 100-C23

5098

267

22C-D022N103 11 (15)

22

340-528 19.2 23

30

140M-F8E-C32 100-C30

5098

329

22C-D030N103 15 (20)

27

340-528 25.8 31

40

140M-F8E-C32 100-C37

5098

435

22C-D038A103 18.5 (25) 38

340-528 33.3 40

50

140M-F8E-C45 100-C60

9086

606

22C-D045A103 22 (30)

45.5

340-528 39.1 47

60

100-C60

738

22C-D060A103 30 (40)

54

340-528 53.3 64

80

100-C85

664

22C-D072A103 37 (50)

72

340-528 60.7 73

100

100-C85

1019

22C-D088A103 45 (60)

88

340-528 74.9 90

125

100-D110

1245

22C-D105A103 55 (75)

105

340-528 89

107

150

100-D140

1487

22C-D142A103 75 (100)

128

340-528 124.8 150

200

100-D180

2043

22C-D170A103 90 (125)

170

340-528 142

170

250

100-D250

2617

22C-D208A103 110 (150) 208

340-528 167

200

250

100-D250

3601

(1)

Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(3)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(4)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.