Basic display group parameters, Smart start-up with basic program group – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 18

Advertising
background image

English-18

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

The Basic Program Group contains the most commonly changed parameters.

The PowerFlex 400 is designed so that start up is simple and efficient. The Program Group
contains the most commonly used parameters.

Basic Display Group Parameters

No.

Parameter

Min/Max

Display/Options

b001 [Output Freq]

0.00/[Maximum Freq]

0.01 Hz

b002 [Commanded Freq]

0.00/[Maximum Freq]

0.01 Hz

b003 [Output Current]

0.0/(Drive Amps

×

2)

0.1 Amps

b004 [Output Voltage]

0/510

1 VAC

b005 [DC Bus Voltage]

0/820

1 VDC

b006 [Drive Status]

0/1 (1 = Condition True)

Bit 4

Bit 3

Bit 2

Bit 1

Decelerating

Accelerating

Forward

Running

b007 [Fault 1 Code]

0/122

1

b008 [Process Display]

0.00/9999.99

0.01

b010 [Output Power]

0.0/999.9 kW

0.1 kW

b011 [Elapsed MWh]

0/3276.7 MWh

0.1 MWh

b012 [Elapsed Run Time]

0/9999 Hrs

1 = 10 Hrs

b013 [Torque Current]

0.0/(Drive Amps

×

2)

0.1 Amps

b014 [Drive Temp]

0/120 degC

1 degC

b015 [Elapsed kWh]

0.0/100.0 kWh

0.1 kWh

Smart Start-Up with Basic Program Group

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

P031 [Motor NP Volts]

20/Drive Rated Volts

1 VAC

Based on Drive Rating

Set to the motor nameplate rated volts.

P032 [Motor NP Hertz]

15/320 Hz

1 Hz

60 Hz

Set to the motor nameplate rated frequency.

P033 [Motor OL Current]

0.0/(Drive Amps

×

2)

0.1 Amps

Based on Drive Rating

Set to the maximum allowable motor current.

P034 [Minimum Freq]

0.0/320.0 Hz

0.1 Hz

0.0 Hz

Sets the lowest frequency the drive will output
continuously.

P035 [Maximum Freq]

0.0/320.0 Hz

0.1 Hz

60.0 Hz

Sets the highest frequency the drive will output.

P036 [Start Source]

0/6

0 = “Keypad”
1 = “3-Wire”
2 = “2-Wire”
3 = “2-W Lvl Sens”
4 = “2-W Hi Speed”
5 = “Comm Port”
6 = “2-W Lvl/Enbl”

3

Sets the control scheme used to start the drive
when in Auto/Remote mode.

P037 [Stop Mode]

0/7

0 = “Ramp, CF”

(1)

1 = “Coast, CF”

(1)

2 = “DC Brake, CF”

(1)

3 = “DCBrkAuto,CF”

(1)

4 = “Ramp”
5 = “Coast”
6 = “DC Brake”
7 = “DC BrakeAuto”

(1)

Stop input also clears active fault.

0

Active stop mode for all stop sources [e.g. keypad,
run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to
stop input except when P036 [Start Source] is set
for “3-Wire” control. When in three wire control, I/O
Terminal 01 is controlled by P037 [Stop Mode].