Aux relay card group parameters – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 23

Advertising
background image

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-23

A182 [Drive OL Mode]

0/3

0 = “Disabled”
1 = “Reduce CLim”

2 = “Reduce PWM”
3 = “Both-PWM 1st”

3

A183 [SW Current Trip]

0.0/(Drive Amps

×

1.8) 0.1 Amps

0.0 (Disabled)

A184 [Load Loss Level]

0.0/Drive Amps

0.1 Amps

0.0 (Disabled)

A185 [Load Loss Time]

0/9999 Secs

1 Secs

0 (Disabled)

A186 [Stall Fault Time]

0/5

0 = “60 Seconds”
1 = “120 Seconds”
2 = “240 Seconds”

3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”

0

A187 [Bus Reg Mode]

0/1

0 = “Disabled”

1 = “Enabled”

1

A188 [Skip Frequency 1]

0/320 Hz

1 Hz

0 Hz

A189 [Skip Freq Band 1]

0.0/30.0 Hz

0.1 Hz

0.0 Hz

A190 [Skip Frequency 2]

0/320 Hz

1 Hz

0 Hz

A191 [Skip Freq Band 2]

0.0/30.0 Hz

0.1 Hz

0.0 Hz

A192 [Skip Frequency 3]

0/320 Hz

1 Hz

0 Hz

A193 [Skip Freq Band 3]

0.0/30.0 Hz

0.1 Hz

0.0 Hz

A194 [Compensation]

0/3

0 = “Disabled”
1 = “Electrical”

2 = “Mechanical”
3 = “Both”

3

A195 [Reset Meters]

0/2

0 = “Ready/Idle”

1 = “Reset MWh”
2 = “Reset Time”

0

A196 [Testpoint Sel]

1024/65535

1

1024

A197 [Fault Clear]

0/2

0 = “Ready/Idle”

1 = “Reset Fault”
2 = “Clear Buffer”

0

A198 [Program Lock]

0/3

0 = “Unlocked”
1 = “Locked” (All)

2 = “Locked” (Not Network)
3 = “Locked” (P035, A170)

0

A199 [Motor NP Poles]

2/40

1

4

A200 [Motor NP FLA]

0.1/(Drive Amps

×

2)

0.1 Amps

Rated Amps

No.

Parameter

Min/Max

Display/Options

Default

Aux Relay Card Group Parameters

No.

Parameter

Min/Max

Display/Options

Default

R221
R224
R227
R230
R233
R236

[Relay Out3 Sel]
[Relay Out4 Sel]
[Relay Out5 Sel]
[Relay Out6 Sel]
[Relay Out7 Sel]
[Relay Out8 Sel]

0/23

0 = “Ready/Fault”
1 = “At Frequency”
2 = “MotorRunning”
3 = “Hand Active”
4 = “Motor Overld”
5 = “Ramp Reg”
6 = “Above Freq”
7 = “Above Cur”
8 = “Above DCVolt”

9 = “Above Anlg 2”
10 = “Above PF Ang”
11 = “Anlg In Loss”
12 = “ParamControl”
13 = “Retries Exst”
14 = “NonRec Fault”
15 = “Reverse”
16 = “Logic In 1”
17 = “Logic In 2”
23 = “Aux Motor”

0

R222
R225
R228
R231
R234
R237

[Relay Out3 Level]
[Relay Out4 Level]
[Relay Out5 Level]
[Relay Out6 Level]
[Relay Out7 Level]
[Relay Out8 Level]

0.0/9999 Hz

0.1

0.0

R239 [Aux Motor Mode]

0/1

0 = “Disabled”

1 = “Enabled”

0

R240 [Aux Motor Qty]

1/6

1 = “1 Aux Mtr”
2 = “2 Aux Mtr”
3 = “3 Aux Mtr”

4 = “1 Mtr + Swap”
5 = “2 Mtr + Swap”
6 = “3 Mtr + Swap”

1

R241
R244
R247

[Aux 1 Start Freq]
[Aux 2 Start Freq]
[Aux 3 Start Freq]

0.0/320.0 Hz

0.1 Hz

50.0 Hz

[Relay OutX Select] Setting

[Relay OutX Level] Min/Max

6

0/320 Hz

7

0/180%

8

0/815 Volts

9

0/100%

10

1/180 degs

12

0/1