Figure 1, Figure 2, General grounding requirements – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual
Page 3: Minimum mounting clearances, Frame d & e frame f
Advertising
PowerFlex 400 Adjustable Frequency AC Drive Quick Start
English-3
Minimum Mounting Clearances
Figure 1: Frame C Mounting Clearances
Figure 2: Frames D, E and F Mounting Clearances
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
120 mm
(4.7 in.)
25 mm
(1.0 in.)
Mounting Option B
Mounting Option A
No clearance required
between drives.
150 mm
(6.0 in.)
150 mm
(6.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
250 mm
(9.8 in.)
150 mm
(6.0 in.)
50 mm
(2.0 in.)
50 mm
(2.0 in.)
Frame D & E
Frame F
General Grounding Requirements
PE
L1
R
L2
S
L3
T
T1
U
T2
V
T3
W
PE
Required
Input Fusing
Required Branch
Circuit Disconnect