PowerFlex 400 Adjustable Frequency AC Drive Quick Start

English-7

Figure 3: Power Terminal Blocks

Power Wiring

Terminal

(1)

Description

R/L1, S/L2, T/L3 3-Phase Input
U/T1

To Motor U/T1

=

Switch any two motor
leads to change
forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

P2, P1

DC Bus Inductor Connection

Drives are shipped with a jumper between Terminals
P2 and P1. Remove this jumper only when a DC Bus
Inductor will be connected. Drive will not power up
without a jumper or inductor connected.

DC–, DC+

DC Bus Connection (Frame C Drives)

P2, DC–

DC Bus Connection (Frame D, E, and F Drives)

BR+, BR–

Not Used
Safety Ground - PE

(1)

Important: Terminal screws may become loose during shipment. Ensure that all
terminal screws are tightened to the recommended torque before applying power to
the drive.

R/L1 S/L2 T/L3

P1

P2

DC– U/T1 V/T2 W/T3

R/L1 S/L2 T/L3 P1

P2

DC– U/T1 V/T2 W/T3

R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P2

P1

BR–

BR+

DC+

DC–

R/L1S/L2T/L3

P1 P2 DC–

U/T1V/T2W/T3

R/L1 S/L2 T/L3 P1

P2 DC–

U/T1 V/T2 W/T3