Ce conformity, Ungrounded distribution systems, Important: tighten screw after jumper removal – Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 4

Advertising
background image

English-4

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Ungrounded Distribution Systems

Phase to Ground MOV Removal

Note: Frame D drives do not contain a MOV to ground connection and
are suitable for operation in both grounded and ungrounded distribution
systems without modification.

Refer to the PowerFlex 400 User Manual supplied with the drive for
details on how to comply with the Low Voltage (LV) and
Electromagnetic Compatibility (EMC) Directives.

EMC Line Filters

!

ATTENTION: PowerFlex 400 drives contain protective MOVs that
are referenced to ground. These devices must be disconnected if the
drive is installed on an ungrounded or resistive grounded distribution
system.

Frame C

Frame E & F

R/L1
S/L2
T/L3

1

2

3

4

Important:
Tighten screw after
jumper removal.

CE Conformity

240V 50/60 Hz 3-Phase

480V 50/60 Hz 3-Phase

kW

HP

Catalog
Number

kW

HP

Catalog
Number

2.2

3.0

22-RF034-CS

2.2

3.0

22-RF018-CS

4.0

5.0

22-RF034-CS

4.0

5.0

22-RF018-CS

5.5

7.5

22-RF034-CS

5.5

7.5

22-RF018-CS

7.5

10

22-RF034-CS

7.5

10

22-RF018-CS

11

15

22-RFD070

11

15

22-RF026-CS

15

20

22-RFD100

15

20

22-RFD036

18.5

25

22-RFD100

18.5

25

22-RFD050

22

30

22-RFD150

22

30

22-RFD050

30

40

22-RFD150

30

40

22-RFD070

37

50

22-RFD180

37

50

22-RFD100

45

60

22-RFD100

55

75

22-RFD150

75

100

22-RFD180

90

125

Consult Factory

110

150

Consult Factory

Advertising