Rockwell Automation 22C PowerFlex 400 AC Drive Quick Start - FRN 1-4.xx User Manual

Page 6

Advertising
background image

English-6

PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Category

Specification

Agency
Certification

Listed to UL508C and CAN/CSA-22.2
Listed to UL508C for plenums

Certified to AS/NZS, 1997 Group 1, Class A

Marked for all applicable European Directives
EMC Directive (89/336)

EN 61800-3, EN 50081-1, EN 50082-2

Low Voltage Directive (73/23/EEC)

EN 50178, EN 60204

The drive is also designed to meet the appropriate portions of the following specifications:

NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and

Operation of Adjustable Speed Drive Systems.

IEC 146 - International Electrical Code.

Protection

Bus Overvoltage Trip:

200-240V AC Input: 405V DC bus voltage (equivalent to 290V AC
incoming line)
380-460V AC Input: 810V DC bus voltage (equivalent to 575V AC
incoming line)

Bus Undervoltage Trip:

200-240V AC Input: 210V DC bus voltage (equivalent to 150V AC
incoming line)
380-480V AC Input: 390V DC bus voltage (equivalent to 275V AC
incoming line)

Power Ride-Thru:

100 milliseconds

Logic Control Ride-Thru:

0.5 seconds minimum, 2 seconds typical

Electronic Motor Overload
Protection:

Provides class 10 motor overload protection according to NEC
article 430 and motor over-temperature protection according to
NEC article 430.126 (A) (2). UL 508C File 29572.

Overcurrent:

180% hardware limit, 220% instantaneous fault

Ground Fault Trip:

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Electrical

Efficiency:

97.5% at rated amps, nominal line voltage

Control

Output Frequency:

0-320 Hz (programmable)

Control
Inputs

Digital:

Quantity:

(3) Semi-programmable
(4) Programmable

Type

Source Mode (SRC):
Sink Mode (SNK):

18-24V = ON, 0-6V = OFF
0-6V = ON, 18-24V = OFF

Analog: Quantity:

(1) Isolated, –10 to 10V or 4-20mA
(1) Non-isolated, 0 to 10V or 4-20mA

Specification

Resolution:
0 to 10V DC Analog:
4-20mA Analog:
External Pot:

10-bit
100k ohm input impedance
250 ohm input impedance
1-10k ohm, 2 Watt minimum

Control
Outputs

Relay:

Quantity:

(2) Programmable Form C

Specification

Resistive Rating:
Inductive Rating:

3.0A at 30V DC, 3.0A at 125V, 3.0A at 240V AC
0.5A at 30V DC, 0.5A at 125V, 0.5A at 240V AC

Optional
Relay
Card:

Quantity:

(6) Optional Programmable Form A (Drive Frames D, E & F Only)

Specification

Resistive Rating:

Inductive Rating:

0.1A at 30V DC Class II circuits, 3.0A at 125V,
3.0A at 240V AC
0.1A at 30V DC Class II circuits, 3.0A at 125V
3.0A at 240V AC

Opto:

Quantity:

(1) Programmable

Specification:

30V DC, 50mA Non-inductive

Analog: Quantity:

(2) Non-Isolated, 0-10V or 4-20mA

Specification

Resolution:
0 to 10V DC Analog:
4-20mA Analog:

10-bit
1k ohm minimum
525 ohm maximum

UL

®

C

US

Advertising