PowerFlex 400 Adjustable Frequency AC Drive Quick Start

Power Terminal Block Specifications

Important: Frame C, D, and F drives utilize a finger guard over the

power wiring terminals. Replace the finger guard when
wiring is complete.

Refer to the PowerFlex 400 User Manual for maximum power cable
length recommendations.

Input Power Conditions

Frame

Maximum Wire Size

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations. If national or local codes require sizes outside this range, lugs may
be used.

Minimum Wire Size

(1)

Recommended
Torque

C

8.4 mm

2

(8 AWG)

1.3 mm

2

(16 AWG)

2.9 N-m (26 lb.-in.)

D

33.6 mm

2

(2 AWG)

8.4 mm

2

(8 AWG)

5.1 N-m (45 lb.-in.)

E

480V
37-45 kW
(50-60 HP)

33.6 mm

2

(2 AWG)

3.5 mm

2

(12 AWG)

5.6 N-m (49.5 lb.-in.)

E

240V
30-37 kW
(40-50 HP)
480V
55-75 kW
(75-100 HP)

107.2 mm

2

(4/0 AWG)

53.5 mm

2

(1/0 AWG)

19.5 N-m (173 lb.-in.)

F

152.5 mm

2

(300 MCM) 85.0 mm

2

(3/0 AWG)

19.5 N-m (173 lb.-in.)

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line
reactance)

Install Line Reactor

(1)

or Isolation Transformer

(1)

Refer to the PowerFlex 400 User Manual for accessory ordering information.

Line has power factor correction capacitors

Install Line Reactor

(1)

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase to ground voltage exceeds 125% of
normal line to line voltage

Remove MOV jumper to ground
(Frame C, E & F drives only)

or Install Isolation Transformer with
grounded secondary if necessary

Ungrounded distribution system