Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Notes

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of
motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are
maximum.

(5)

Bulletin 140M with adjustable current range must have the current trip set to the minimum range that the device will not trip.

(6)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/
347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.

(7)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers can vary. See

Bulletin 140M Motor Protection Circuit Breakers

Application Ratings

.

(8)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(9)

UL Type 12/IP54 (flange mount) heat sink ambient temperature rating is 40° C/ambient of unprotected drive portion (inside
enclosure) is 55° C. The ambient temperature for the UL Type 12/IP54 stand-alone drives is 40° C.

(10)

Must remove top label and vent plate, drive enclosure rating is IP00, NEMA/UL Type Open.

(11)

Drive frames 0…4 temperature rating is for NEMA/UL Type Open. The adhesive top label must be removed to operate drive at this
temperature. Frames 5 & 6 do not have a top label.

(12)

Drives have dual current ratings; one for normal duty applications, and one for heavy duty applications. The drive can be operated at
either rating.

(13)

Note: 600V class drives below 77 Amps (Frames 0…4) are declared to meet the Low Voltage Directive. It is the responsibility of the
user to determine compliance to the EMC directive.

(14)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-
ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations can require a
larger enclosure.

325 Volt DC Input Protection Devices

Drive Catalog
Number

Fr

am

e Hp Rating

PWM
Freq.

Temp.

(1)

DC Input
Ratings

Output Amps

Fuse

Non-Time Delay
Fuse

(2) (11)

ND

HD

kHz

°C

Amps

Cont.

1 Min.

3 Sec.

20BB2P2

0

0.5

0.33

4

50

2

2.2

2.4

3.3

5

JKS-5

20BB4P2

0

1

0.75

4

50

3.8

4.2

4.8

6.4

10

JKS-10

20BB6P8

1

2

1.5

4

50

6.9

6.8

9

12

15

HSJ15

20BB9P6

1

3

2

4

50

9.7

9.6

10.6

14.4

20

HSJ20

20BB015

1

5

3

4

50

16

15.3

16.8

23

30

HSJ30

20BB022

1

7.5

5

4

50

23.3

22

24.2

33

45

HSJ45

20BB028

2

10

7.5

4

50

30

28

33

44

60

HSJ60

20BB042

3

15

10

4

50

45

42

46.2

63

90

HSJ90

20BB052

3

20

15

4

50

55

52

63

80

100

HSJ100

20BB070

4

25

20

4

50

75.3

70

78

105

150

HSJ150

20BB080

4

30

25

4

50

86.8

80

105

140

175

HSJ175

20BN104

(3)

5

40

4

50

114.1

104

115

175

200

HSJ200

30

4

50

85.8

80

120

160

200

HSJ200

20BN130

(3)

5

50

4

50

142.6

130

143

175

200

HSJ200

40

4

50

114.1

104

156

175

200

HSJ200

20BN154

(3)

6

60

4

50

169

154

169

231

300

HSJ300

50

4

50

142.6

130

195

260

300

HSJ300

20BN192

(3)

6

75

4

50

210.6

192

211

288

350

HSJ350

60

4

50

169

154

231

308

350

HSJ350

20BN260

(3)

6

100

2

45

285.3

260

286

390

400

HSJ400

75

2

50

210.6

205

305

410

400

HSJ400

See

page 41

for notes.