Disconnecting MOVs and Common Mode Capacitors

The Powerflex 700 drive contains protective MOVs and Common Mode
Capacitors referenced to ground (see below). To guard against unstable operation
and/or damage, the drive must be properly configured as shown in

Table 9

on

page 44

.

Before proceeding, ensure that all power to the drive has been removed.

IMPORTANT

All PowerFlex 700 drives are shipped with the DC bus common mode capacitors
referenced to ground.

ATTENTION: Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery must perform maintenance/repair of the
system. Failure to comply can result in personal injury and/or equipment
damage.

ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the following points (refer to pages

29

through

30

for locations):

+DC and -DC terminals of the Power Terminal Block

+DC terminal of the Power Block and the chassis

-DC terminal of the Power Terminal Block and the chassis

The voltage must be zero for all three measurements.

ATTENTION: The following information is merely a guide for proper
installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise for
the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during
installation.

R/L1

S/L2
T/L3

DC+

DC–

MOV and AC EMI Capacitor Phase to Ground

Common Mode Capacitor to Ground

Jumper-Wire