Rockwell Automation 20B PowerFlex 700 Installation Instructions - Frames 0…6 User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

55

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Standard Control Option I/O Terminal Designations

No. Signal

Factory
Default

Description

Related
Param.

1

Anlg Volts In 1 (–)

(2)

Isolated

(3)

, bipolar, differential, ±10V, 11 bit & sign,

88k ohm input impedance.

320 -
327

2

Anlg Volts In 1 (+)

3

Anlg Volts In 2 (–)

(2)

Isolated

(4)

, bipolar, differential, ±10V, 11 bit & sign,

88k ohm input impedance.

4

Anlg Volts In 2 (+)

5

Pot Common

For (+) and (–) 10V pot references.

6

Anlg Volts Out 1 (–)

(2)

Bipolar,

±10V, 11 bit & sign, 2k ohm minimum load.

340 -
344

7

Anlg Volts Out 1 (+)

8

Anlg Current Out 1 (–)

(2)

4-20mA, 11 bit & sign, 400 ohm maximum load.

9

Anlg Current Out 1 (+)

10

Reserved for Future Use

11

Digital Out 1 – N.C.

(1)

Fault

Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA

380 -
387

12

Digital Out 1 Common

13

Digital Out 1 – N.O.

(1)

NOT Fault

14

Digital Out 2 – N.C.

(1)

NOT Run

15

Digital Out 2 Common

16

Digital Out 2 – N.O.

(1)

Run

17

Anlg Current In 1 (–)

(2)

Isolated

(3)

, 4-20 mA, 11 bit & sign, 124 ohm input

impedance.

320 -
327

18

Anlg Current In 1 (+)

19

Anlg Current In 2 (–)

(2)

Isolated

(4)

, 4-20 mA, 11 bit & sign, 124 ohm input

impedance.

20

Anlg Current In 2 (+)

21

–10VDC Pot Ref.

2k ohm minimum.

22

+10VDC Pot Ref.

23

Reserved for Future Use

24

+24VDC

(5)

Drive supplied logic input power.

(5)

25

Digital In Common

26

24V Common

(5)

Common for internal power supply.

27

Digital In 1

Stop - CF

115V AC, 50/60 Hz - Control & I/O Cat. No. option B
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC, 5.0 mA
24V AC/DC, 50/60 Hz- Control & I/O Cat. No. option A
Opto isolated
Low State: less than 5V AC/DC
High State: greater than 20V AC/DC
11.2 mA DC
Digital Input Impedance: 35k ohm

361 -
366

28

Digital In 2

Start

29

Digital In 3

Auto/Man.

30

Digital In 4

Speed Sel 1

31

Digital In 5

Speed Sel 2

32

Digital In 6

Speed Sel 3

(1) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to drive and deenergize

(drop out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists and deenergizes when
condition is removed.

(2) These inputs/outputs are dependant on a number of parameters. See “Related Parameters.”

(3) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.

(4) Differential Isolation - External source must be less than 10V with respect to PE.

(5) 150 mA

maximum load designed to power digital inputs only.

Not present on 115V versions.

1

16

32

Advertising