Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Fram

e

Vo

lt

ag

e

Code

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input
Filter Caps

(1) (2)

DC Bus Common
Mode Caps

5

IP54, NEMA Type 12 Drives

C

D
P
R

All

Two green/yellow
wires connected
to chassis ground

Green/yellow wire is
connected to ground

Solid Ground

1. CM Cap jumper wire must be connected to

ground with a metal screw. Verify, and if
necessary:
• Newer Drives - Remove the nylon screw/

spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).

• Older Drives - Remove the

I/O Cassette (see

page 53

). The green/

yellow CM Cap jumper wire is on the back
of chassis and must be connected to
ground with a metal screw. Remove the
insulation from the wire terminal and
connect to chassis with a metal M5 x 10
screw. Torque screw to 3.2 N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires must be

connected to ground with a metal screw.
Verify, and if necessary, remove the nylon
screw/spacer and insert a metal M5 x 12
screw.

Non-Solid Ground

1. CM Cap jumper wire must be insulated from

ground. Verify, and if necessary:
• Newer Drives - Remove the metal screw

and insert a M5 x 15 nylon screw/spacer.

• Older Drives - Remove the

I/O Cassette (see

page 53

).Insulate/secure

jumper wire to guard against unintentional
contact with chassis or components.

2. MOV/Input Filter Cap jumper wires must be

insulated from ground with a nylon screw/
spacer. Verify, and if necessary, remove the
metal screw and insert a M5 x 20 nylon screw/
spacer.

Frame 5 continued on next page

(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.

(2) When removing MOV’s, the input filter capacitor must also be removed.

USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)

POWER & DC TERMINAL RATINGS

WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)

BRAKE TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (18-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

OUTPUT

INPUT AC

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

DANGER

DANGER

RISK OF ELECTRIC
SHOCK AND DEATH

FIELD INSTALLED OPTIONS

6 MM HEX KEY

6 MM HEX KEY

SHLD

SHLD

MOV

MOV / Input Filter Cap

CM Cap -
Older Drives

CM Cap - Newer Drives