PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

I/O Wiring Examples

Input/Output

Connection Example

Required Parameter Changes

Potentiometer Unipolar
Speed Reference

(1)

10k Ohm Pot. Recommended
(2k Ohm Minimum)

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results:

Parameter 002

Joystick Bipolar Speed
Reference

(1)

±10V Input

• Set Direction Mode:

Parameter 190 = “1, Bipolar”

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results:

Parameter 002

Analog Input Bipolar
Speed Reference
±10V Input

• Set Direction Mode:

Parameter 190 = “1, Bipolar”

• Adjust Scaling:

Parameters 91/92 and 325/326

• View Results:

Parameter 002

Analog Voltage Input
Unipolar Speed Reference
0 to +10V Input

• Configure Input with parameter 320

• Adjust Scaling:

Parameters 91/92 and 325/326

• View results:

Parameter 002

Analog Current Input
Unipolar Speed Reference
0-20 mA Input

• Configure Input for Current:

Parameter 320 and add jumper at
appropriate terminals

• Adjust Scaling:

Parameters 91/92 and 325/326

• View results:

Parameter 002

Analog Input, PTC
PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V

• Set Fault Config 1:

Parameter 238, bit 7 = “Enabled”

• Set Alarm Config 1:

Parameter 259, bit 11 = “Enabled”

• View Status Drive Alarm 1:

Parameter 211, bit 11 = “True”

HW PTC Input
PTC OT set > 5V
PTC OT cleared < 4V
PTC Short < 0.2V

• Set Fault Config 1:

Parameter 238, bit 13 = “Enabled”

• Set Alarm Config 1:

Parameter 259, bit 18 = “Enabled”

• View Status: Drive Alarm 1:

Parameter 211, bit 18 = “True”

Analog Output
±10V, 0-20 mA Bipolar
+10V Unipolar (shown)

• Configure with Parameter 340

• Select Source Value:

Parameter 380, [Digital Out1 Sel]

• Adjust Scaling:

Parameters 343/344

2-Wire Control Non-
Reversing

(2)

24V DC internal supply

• Disable Digital Input:#1:

Parameter 361 = “0, Unused”

• Set Digital Input #2:

Parameter 362 = “7, Run”

• Set Direction Mode:

Parameter 190 = “0, Unipolar”

3
4
5

22

3

5

21
22

3
4

Common

+

3
4

Common

+

3
4

19
20

Common

+

5

3.32k

Ohm

1.8k

PTC

Ferrite

Bead

1
2

22

1.8k

PTC

Ferrite

Bead

10

23

+

24
25
26

28

Stop-Run