PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Attain Manual Control

Close the digital input.
With the input closed, the speed command comes from the HIM.

Release to Auto Control

Open the digital input.
With the input open, the speed command returns to the PLC.

Auto/Manual Notes

1.

Manual control is exclusive. If a HIM or terminal block takes manual
control, no other device can take manual control until the controlling
device releases manual control.

2.

If a HIM has manual control and power is removed from the drive, the
drive returns to Auto mode when power is reapplied.

3.

Parameter 192 - [Save HIM Ref ], bit 1 can enable Manual mode to allow
starts and jogs from the HIM in 2-wire mode.

Step 5: Start-Up Check List

This check list supports the Basic Start-Up menu option. See

page 67

for

information on other start-up routines.

A Human Interface Module (HIM) is required to run the Basic Start-Up
routine.

The Basic Start-Up routine can modify parameter values for Analog and
Digital I/O. Refer to Common I/O Programming Changes on

page 71

.

Prepare For Drive Start-Up

1.

Confirm that all inputs are connected to the correct
terminals and are secure.

2.

Verify that AC line power at the disconnect device is
within the rated value of the drive.

3.

Verify that control power voltage is correct.

4.

The remainder of this procedure requires that a
HIM be installed. Connect a Human Interface
Module (HIM) to Drive Peripheral Interface (DPI)
Port 1 or 2. Use remote devices to start up the drive,
if an operator interface is not available.

ATTENTION: Power must be applied to the drive to perform the following
start-up procedure. Some of the voltages present are at incoming line potential.
To avoid electric shock hazard or damage to equipment, only qualified service
personnel must perform the following procedure. Thoroughly read and
understand the procedure before beginning.

Esc

7

8

9

4

5

6

1

2

3

.

0

+/-

Sel

Jog

Alt

POWER

STS

PORT

MOD

NET A

NET B

Exp

Param #

S.M.A.R.T.

Exit

Lang

Auto / Man

Remove

HOT surfaces can cause severe burns

CAUTION

DPI Ports and