Drive identification, Jumper settings and locations, Cm cap mov – Rockwell Automation 20B PowerFlex 700 Installation Instructions - Frames 0…6 User Manual

Page 45: Cm cap

Advertising
background image

Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

45

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Drive Identification

Refer to the drive nameplate and locate
the “Voltage Code,” “Current Rating,”
“Frame,” and “UL Type” (Frames 5…6).
Use this information to locate the
proper procedure in the following
tables.

Jumper Settings and Locations

Cat No. 20B

D xxx

x x xxxxxxx

Made in the USA (TAC 1J)
Rockwell Automation, Mequon WI 53092-4400

UL TYPE 1/IP20

Mfd. in 2007 on Aug 1

Frame:

3

Serial Number: xxxxxxx

Series: B

I/O: 24VAC/DC (Standard)
Original Firmware V. x.xxx

Listed

Ind. Cont
Eq. 966X

U

c

US

L

®

Normal Duty Power
Heavy Duty Power

AC Voltage Range
Amps

Input: 3 Phase, 47-63Hz

Output: 3 Phase, 0-400 Hz

AC Voltage Range
Base Hz (default)
Continuous Amps
1 Min Overload Amps
3 Sec Overload Amps

xxx kW
xxx kW

342-440

xxx

0-400
50 Hz

xxx
xxx
xxx

xxx kW
xxx kW

432-528

xxx

400V

480V

0-460
60 Hz

xxx
xxx
xxx

N223

Voltage Code

Frame

Current Rating

UL Type

Series

Fram

e

Vo

lt

ag

e

Code

Cu

rrent

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input
Filter Caps

DC Bus Common
Mode Caps

0…1

All Drives

B…E

All

PE_B
Installed

PE_A
Installed

Solid Ground

• Remove the I/O Cassette (see

page 53

). Verify

that jumpers are installed at the “PE_A” and
“PE_B” locations on the Power Board.

Non-Solid Ground

• Remove the I/O Cassette (see

page 53

).

Remove jumpers at the “PE_A” and “PE_B”
locations on the Power Board.

2

B…E

All

PE_MOV
Installed

PE_CAP
Installed

Solid Ground

• Verify that jumpers are installed at the

“PE_CAP” and “PE_MOV” locations.

Non-Solid Ground

• Remove jumpers at the “PE_CAP” and

“PE_MOV” locations.

BR1

BR2

DC+

DC–

PE

U/T1

V/T2

W/T3

R/L1

S/L2

T/L3

Use 75C

Wir

e O

nly

#10-#14 A

WG

Tor

que t

o 7 in-lbs

!

DANGER

PE A

PE B

CM Cap

MOV

BR1 BR2 DC+ DC- U/T1 V/T2 W/T3

SHLD

SHLD

PE R/L1 S/L2 T/L3

PE 2

MOV-PE JMPR

PE 1

AUX IN+ AUX OUT–

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTROL

PO

WER

PE 4

PE 3

MOV

PE_MOV

CM Cap

PE_CAP