Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

51

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Fram

e

Vo

lt

ag

e

Code

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input
Filter Caps

(1) (2)

DC Bus Common
Mode Caps

6

IP20, NEMA/UL Type 1 and Open Drives (continued)

E
F
T

W

All

Two green/yellow
wires connected
to Power Terminal
Block “PE” and
chassis

Green/yellow wire to
CM Cap Board is
connected to Power
Terminal Block “PE”

Solid Ground

1. The green/yellow CM Cap and MOV jumper

wires must be connected to “PE.”

2. The Input Filter Cap jumper wire (top right)

must be connected to chassis ground with a
metal screw. Verify, and if necessary, remove
the nylon screw/spacer and insert a metal M5
x 10 screw. Torque to 3.2 N•m (28 lb•in).

Non-Solid Ground

1. The green/yellow CM Cap and MOV jumper

wires must be insulated from ground. Verify,
and if necessary, remove them from “PE” and
individually insulate/secure each jumper wire
to guard against unintentional contact with
chassis or components. Important: Do Not
Remove/Disconnect the larger green/
yellow wire
.

2. The Input Filter Cap jumper wire (top right)

must be insulated from ground with a nylon
screw/spacer. Verify, and if necessary, remove
the metal screw and insert a M5 x 15 nylon
screw/spacer.

6

IP54, NEMA Type 12 Drives

C

D

E
F
P
R
T

W

All

Two green/yellow
wires connected
to Power Terminal
Block “PE”

Green/yellow wire to
CM Cap Board is
connected to Power
Terminal Block “PE”

Solid Ground

1. The green/yellow CM Cap jumper wire must be

connected to “PE.”

2. The MOV/Input Filter Cap jumper wires must

be connected to “PE.”

Non-Solid Ground

1. The green/yellow CM Cap jumper wire must be

insulated from ground. Verify, and if necessary,
remove the jumper wire from “PE” and
insulate/secure it to guard against
unintentional contact with chassis or
components. Important: Do Not Remove/
Disconnect the larger green/yellow wire
.

2. MOV/Input Filter Cap jumper wires must be

insulated from ground. Verify, and if necessary,
remove the jumper wires from “PE” and
individually insulate/secure them to guard
against unintentional contact with chassis or
components.

(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.

(2) When removing MOV’s, the input filter capacitor must also be removed.

DC–

DC+

BR1

BR2

USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)

22-10
AWG

5.3 IN-LB
(0.6 N-M)

WIRE STRIP

PS+

PS

USE 75 C

COPPER WIRE

ONLY

TORQUE
52 IN-LB
(6 N-M)

U

T1

V

T2

W
T3

R

L1

S

L2

INPUT

OUTPUT

T

L3

PE

PE

Optional

Communications

Module

Input Filter Cap

PE

PE

MOV

CM Cap

DO NOT
REMOVE

MOV

U

T1

V

T2

W
T3

R

L1

S

L2

INPUT

OUTPUT

T

L3

PE

PE

PE

PE

MOV

Input Filter Cap

CM Cap

DO NOT
REMOVE