I/O Terminals

The figure below shows the I/O Control Cassette and terminal block locations.
The cassette provides a mounting point for the various PowerFlex 700
I/O options. To remove the cassette, follow the steps below. Cassette removal is
similar for all frames (Frame 0 drive shown).

PowerFlex 700 Typical Cassette & I/O Terminal Blocks

I/O Terminal Block Specifications

Step

Description

Disconnect the two cable connectors shown below.

Loosen the two screw latches shown below.

Slide the cassette out.

Remove screws securing cassette cover to gain access to the boards.

No.

Name

Description

Wire Size Range

(1)

(1) Maximum/minimum that the terminal block accepts - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

I/O Cassette

Removable I/O Cassette

I/O Terminal Block

Signal & control
connections

2.5 mm

2

(14 AWG)

0.30 mm

2

(22 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)

Encoder Terminal
Block

Encoder power & signal
connections

0.75 mm

2

(18 AWG)

0.196 mm

2

(24 AWG)

0.6 N•m
(5.3 lb•in)

0.6 N•m
(5.3 lb•in)

A

B

C

D

BR1

BR2

DC+

DC-

PE

U/T1

V/T2

W/T3

R/L1

L2

=

A

Pin 1

Detail

B

C

D

B