Rockwell Automation 161 SERIES A User Manual

Page 12

Advertising
background image

Bulletin 161

6

4.1 Connection and description of the power terminals


The control unit must be open in order to be able to wire the power terminals. Do not apply mains voltage to the
drive connection terminals U/T1, V/T2, and W/T3 as this will result in damage to equipment. The Bulletin
161 drives feature an electronic overload protection to monitor the drive current. In the case of multi-motor
operation, thermal contacts or PTC resistors must be used for each motor. In the case of motor lead lengths >
50 m motor reactors should be used.

Connection example Bulletin 161







AC Line Input fuse ratings or other Line Side Protective Devices:


Fuse Rating

Circuit Breaker Type and Rating


Bulletin 161S-AA01 – AA03

: 10 A time-lag

140-MN-1000 / 140M-D8N-C10

Bulletin 161S-AA04 – AA07

:

16 A time-lag

140-MN-1600 / 140M-D8N-C16

Bulletin 161S-AA10

:

25 A time-lag

140-MN-2500 / 140M-D8N-C25

Mains power supply

Connection for optional
brake chopper

Bulletin 161

Line filter EMC