Bulletin 161

8

4.2 Connection and description of the control terminals


When using the transistor outputs 11, 12 - CM2 install a recovery diode parallel to the relay used. Otherwise
the switching relay could damage the output. Do not short-circuit the terminals H and L or P24 and L.

The control wires must be installed separately from the power lines and motor lines. They may not exceed 20
m in length. To improve noise immunity, the control wires should be screened
(refer to Appendix A).
If unavoidable, transpositions between the power lines or motor lines and the control wires should be installed
at right angles.

Example of a connection

Wait at least 2s after turning on the power supply before issuing a start command and do not switch

off the mains supply during operation of the device.

Each signal must be applied to the digital inputs 1 …5 for at least 12 ms.

If input 5 is programmed as a PTC resistor (parameter

C05

), terminal L will be the corresponding

reference potential.

pot 1 - 2 k

frequency reference

fault indication relay

230 VAC