Rockwell Automation 161 SERIES A User Manual

Page 17

Advertising
background image

Bulletin 161

11

Overview of the functions of the programmable digital inputs 1 - 5


The digital inputs 1 to 5 can be programmed for 15 different functions. With exception of the PTC input
(programmable on input 5 only), every input can be programmed for any function. Parameters cannot be
programmed for two different inputs at the same time. The various functions are listed and described in the table
below. Programming is done via parameters

C01...C15

(parameters

C01...C05

correspond to inputs 1 to 5; pro-

gramming for normally closed NC contacts or norm. open contacts NO is carried out via parameters

C11...C15

).

Input /

Function

Function

Description

[FW]

00

Forward

Start/stop forward (see parameter

A0

2)

[RV]

01

Reverse

Start/stop reverse (see parameter

A0

2)

[CF1]

02


The pre-set frequencies may be programmed in two ways:
1.) by entering the frequencies under parameter

A

2

1...A35

.

2.) by selecting the corresponding digital input [CF1] ... [CF4] and

[CF2]

03


Preset frequencies

entering the required frequency under parameter

F01

. Press the ENTER

key to store the value entered. Press the SEL key to check that the value
entered has been stored.

[CF3]

04



[CF4]

05



[2CH]

09

2

nd

Accel/Decel ramp

2

nd

acceleration/deceleration time (parameter

A9

2,

A93

)

[FRS]

11

Controller lock

The motor voltage will be switched off immediately – the motor will coast
(isolation of motor e.g. emergency).
For [FRS] two operation modes can be selected under parameter

b88

1. Synchronisation of the motor speed after the waiting period

programmed under parameter

b03

is over (enter

01

).

2. 0 Hz start after activating [FRS] (enter

00

).


[EXT]

12

External fault

When this input is addressed, a fault indication will be issued (

E12

, e.g. to

be used as the input for thermal contacts)
The fault indication will be cleared with Reset.
Attention! After reset the drive will start again if a start command has
been issued ([FW] or [RV]).

Input

Preset Speed

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

CF1

ON

ON

ON

ON

ON

ON

ON

ON

CF2

ON

ON

ON

ON

ON

ON

ON

ON

CF3

ON

ON

ON

ON

ON

ON

ON

ON

CF4

ON

ON

ON

ON

ON

ON

ON

ON

[FW], [RV]

input [FRS]

motor speed

waiting time

0Hz start

synchronisation of
the motor speed

Motor will
coast

Motor speed

[FW], [RV]

Input [EXT]

Input [RS] (Reset)

Fault indication relay (AL0-AL2)

Advertising