Bulletin 161

19

Parameter
number

Function

Basic
value

Setting range

Input

PID controller

A71

PID controller active / inactive

00

00: inactive
01: active

A72

PID Proportional Gain

1.0

0.2 – 5.0

A73

PID Integral Gain

1.0

0.0 - 150 s

A74

PID Differential Gain

0.0

0.0 - 100

A75

Process reference scale factor

1.0

0.01 – 99.99

A76

Process analog feedback

00

00: input OI
01: input O

Automatic voltage regulation (AVR)

A81

AVR function select

02

00: active
01: inactive
02: not active in

deceleration

A82

Motor voltage / AVR- voltage

230

200 - 240 V

Second acceleration / deceleration ramp

A92

2

nd

Acceleration time

15

0.1 - 3000 s

A93

2

nd

Deceleration time

15

0.1 - 3000 s

A94

Select 2

nd

acceleration / deceleration ramp

00

00: input set to [2CH]
01: Automatic if freq.

programmed in
param.

A95 / A96

is reached

A95

2

nd

acceleration ramp starting frequency

0.0

0.0 - 360 Hz

A96

2

nd

deceleration ramp starting frequency

0.0

0.0 - 360 Hz

A97

Acceleration Curve

00

00: linear
01: S-curve

A98

Deceleration Curve

00

00: linear
01: S-curve