Technical data – Rockwell Automation 161 SERIES A User Manual

Page 33

Advertising
background image

Bulletin 161

27

8. Technical Data

Series

Bulletin 161S-

Type

AA01

AA02

AA03

AA04

AA05

AA07

AA10

Drive rating (kW)

0.2

0.4

0.55

0.75

1.1

1.5

2.2

Input rated current (A)

3.1

5.8

6.7

9.0

11.2

16.0

22.5

Output rated current (A)

1.4

2.6

3.0

4.0

5.0

7.1

10.0

Mass (kg)

0.85

0.85

1.3

1.3

2.2

2.2

2.8

Mains voltage (V)

1 ~ 200 V -10% to 240 V + 5%, 50/60 Hz +/- 5%

Output voltage

3 ~ 0 - 200 ... 240 V in accordance with the mains voltage

Type of protection

IP20

PWM carrier frequency

0.5 - 16 kHz

V/F characteristics

V/F characteristics for constant torque and variable torque; variable output voltage,
Base Frequency and Maximum Frequency.

Type of control

Voltage-driven, PWM sinus coded, IGBT-Power module

Output frequency

0.5 - 360 Hz

Accuracy of frequency
command

Digital: +/- 0.01% of max. frequency
Analog: +/- 0.2% of max. frequency

Frequency resolution

Digital: 0.1%, analog: max. frequency/1000

Overload capacity

150% for 60 s (once in a period of 10 min.), max. 220%

Starting torque

min. 150% at frequencies >3 Hz

Braking torque by
feeding back into the
capacitors

Bulletin 161S-AA01 ... AA04:

100%

Bulletin 161S-AA05 ... AA07:

70%

Bulletin 161S-AA10:

20%

DC brake

Starting frequency, braking torque, running time are variable.

Analog inputs

0 -10 V, input impedance 10 k

4 - 20 mA, input impedance 250

PTC input

Digital inputs

5 free programmable inputs, 24 V PNP logic, NO contacts or NC contacts

Analog outputs

1 analog output to either display the output frequency or the motor current.
For output frequency can be switched as an impulse output.

Digital outputs

2 open collector outputs for (for either operation indication, at frequency / above
frequency, overload alarm, PID controller deviation exceeded).
1 fault indication relay (change-over contact)

Protection functions

Overcurrent, overvoltage, under-voltage, electronic motor protection,
overtemperature, earth fault, overload etc.

Other functions

15 preset speeds, PID controller, parameter protection, restart lock,
RS422 serial interface, skip frequencies etc.

Ambient temperature

-10 - +40 °C (up to +50 °C in the case of reduction of reference frequency
to < 2 kHz, restriction of output current to 80% and removal of top cover)

Relative humidity

20 - 90% relative humidity, no condensation

Vibration/shock

5.9 m/s

2

(0.6 G) 10 - 55 Hz

Max. installation altitude 1000 m above sea level

Options

Line filter modules

Standards

EN 61800-3 EMC guidelines in connection with optional line filter modules
in line with installation guidelines,
EN 50178 Low-Voltage guideline,
UL