Rockwell Automation 161 SERIES A User Manual

Page 24

Advertising
background image

Bulletin 161

18

Parameter
number

Function

Basic
value

Setting range

Input

V/F characteristics / boost

A41

Boost select

00

00: Man. boost
01: Auto boost

A42

Manual boost

11

0 – 99

A43

Max. boost at % of base frequency

10

0 - 50%

A44

V/F select

00

00: Constant
01: Variable

A45

Maximum output voltage

100

50 - 100%

DC brake

A51

DC Brake active / inactive

00

00: inactive
01: active

A52

DC Brake
Starting frequency

0.5

0.5 – 10 Hz

A53

DC Brake
Waiting time

0.0

0 - 5 s

A54

DC Brake
Braking torque

0

0 - 100%

A55

DC Brake
Braking time

0.0

0 - 60 s

Operating frequency range

A61

Maximum Frequency

0.0

0.5 - 360 Hz

A62

Minimum Frequency

0.0

0.5 - 360 Hz

A63

1

st

Skip Frequency

0

0 - 360 Hz

A64

1

st

Skip Frequency Band

0.5

0 - 10 Hz

A65

2

nd

Skip Frequency

0

0 - 360 Hz

A66

2

nd

Skip Frequency Band

0.5

0 - 10 Hz

A67

3

rd

Skip Frequency

0

0 - 360 Hz

A68

3

rd

Skip Frequency Band

0.5

0 - 10 Hz

Advertising