Bulletin 161

15

ATTENTION

Before switching on the power supply the following points must be
observed:

Check that the mains lines and motor lines are connected properly.

The control wires must be connected at the correct terminals.

The drive must be earthed correctly and must be installed vertically on a wall made from non-

flammable material.

All screws and terminals must be tightened.

Check that the connected motor is designed for the frequency range in question, particularly for the

maximum frequency.



5.2 Entering the factory defaults (initialisation)


On supply, all the Bulletin 161 drives are initialized, i.e. they are programmed with the default factory
parameters. The devices may however be re-programmed to these basic settings at any time.

Ensure that the function 01 is stored under parameter

b85

(

01

on initialisation the data of the European

defaults are loaded).

Enter function 01 under parameter

b84

and save this by pressing the ENTER key.

Press

the

8

,

9

and SEL-key at the same time.


While you are pressing the keys mentioned above, briefly press the STOP key and wait approx. 2 - 3 s
until the following is flashing:

d00

.

Now release the three keys. During initialisation the following will be displayed:


The end of initialisation will be indicated by

00

.



5.3 Putting the device into operation via the integrated control panel


The integrated control panel enables the Bulletin 161 drive to be controlled without the additional use of the
control terminals.

Enter function 00 under parameter

A01

(set frequency command via the integrated potentiometer) or 02

(enter the frequency under parameter

F01

).

Program the function 02 under parameter

A02

. The drive can now be started by pressing the START key.

The required direction of rotation can be selected under parameter

F04

(

00

Forward,

01

Reverse).



5.4 Clearing faults/Reset


There are three different ways of clearing fault indications:

Reset input

Switch off power supply

Press the STOP key.