Bulletin 161

12

Input /

Function

Function

Description

[USP]

13

Restart lock

The restart lock prevents a uncontrolled restart of the Bulletin 161 drive
when – after power off – the power supply returns and a start command is
issued immediately or straight afterwards. In this case the following fault
indication will be given:

E13


A new start command or a reset will clear the fault indication.

[SFT]

15

Parameter protection

Parameter protection protects parameters entered from being lost by
overwriting. If the software protection is activated, no data can be lost (see
parameter

b31

).

[AT]

16

Frequency command
input OI active
(4-20 mA)

In the factory default input O (0-10V) is active. Switching to OI is effected
via input [AT]. If there is no digital input programmed as [AT], the
frequency command values are added to O and OI (see parameter

A01

).

[RS]

18

Reset

Clearing a fault indication; reset the fault indication relay. If a reset
command is given during operation, the terminal stages are switched off
and the motor will coast.

[JG]

06

Jog

Jog control is used e.g. to set up a machine manually. This is done via the
inputs [FW] or [RV] if the input [JG] is controlled. When a start command
is given, the frequency programmed under parameter

A38

will be switched

directly to the motor – the start ramp is not active. For the stop command,
three different modes can be selected under parameter

A39

:

1.) The motor will coast
2.) The motor is slowed down at the deceleration ramp
3.) Braking of the motor using the DC brake (see parameter

A54

,

A55

)


Jog control will not be possible if the jog frequency set is less than the start
frequency entered under parameter

b82

.

[PTC]

19

PTC input
Only in connection
with input 5

Reference potential
is terminal L

Input 5 can be programmed as a PTC input under parameter

C05

.

In this case, terminal L will be the reference potential (in all other cases the
reference potential will be at terminal P24).





Output frequency

Start command [FW, RV]

Power supply

Fault indication relay

Input [USP]

Input [RS]

Input [JG]

Fault indication relay

Start command [FW], [RV]

Motor speed

L

5

If the PTC resistance exceeds 3 k

, the motor

will be switched off and the fault indicator

E35

(ERROR PTC) will be issued.