Bulletin 161

10

Terminal

Function

Description

H

10 V reference voltage for
frequency command default

O

Analog input
Frequency command
0-10 V

3RWHQWLRPHWHU

 WR  N2KP

,QSXW LPSHGDQFH

 N2KP

,QSXW LPSHGDQFH

 2KP

+
2

2,

/

+
2

2,

/

+
2

2,

/





 P$

 9



3(

3(

3(

QRPLQDO  9

QRPLQDO  P$

OI

Analog input
Frequency command
4-20 mA

For analog input reference adjustment see parameters

A11...A16.

Input OI for 4-20 mA is activated when the digital input is set to [AT]
(see parameter

C01...C05

).

L

0 V reference potential for
frequency command inputs

If no digital input is programmed as [AT] (switch frequency
command 0-10 V / 4-20 mA), the set values are added to O and OI.

CM2

Reference potential for output
11, 12

Transistor output, max. 27 VDC, 50 mA


The outputs can be programmed as NC contacts or NO contacts
under parameter

C31 or C32

(factory default: NC contact)

11

Programmable
Digital output

Factory default: [FA1]

The following functions may be programmed under the
parameters

C21

and

C21

:

[FA1]: at frequency (Signal when the set value is reached)

[FA2]: above frequency (Signal if output frequencies >/= the

frequencies set under parameter

C42 or C43)

.

[RUN]: Running (Signal if output frequency >0 Hz)

12

Programmable
Digital output

Factory default: [RUN]

[OL]: Motor overload (Signal if the motor current exceeds the value

set under parameter

C41

).

[OD]: PID-deviation (Signal if the deviation between the set value

and the actual value returned is greater than the value set
under parameter

C44

. Only available if the PID controller -

parameter

A71-

is active).

[AL]: Fault (Signal if a fault is indicated. See parameter

C21, C22

)

AL2

AL1


AL0

Relay output
Collective fault

Operation: AL0-AL1 closed
Fault, power off: AL0-AL2 closed (parameter

C33

)

The fault indication relay is set with a time delay of approx. 2 s after
the power is switched on.

250 VAC, 2.5 A resistive
0.2 A cos

= 0.4


30 VDC, 3.0A resistive
0.7 A cos

= 0.4


min. 100 VAC, 10 mA
5 VDC 100 mA