6. Fault indications


The Bulletin 161 drives are provided with protective devices such as protection against excessive current,
excessive voltage and under-voltage. When one of the many protection functions is triggered the output voltage
will be switched off – the motor will freewheel and the device will remain in the fault indication mode until the
fault indication has been cleared.

Fault

indication

Description

Cause

Corrective action

Is the motor rated current larger
than the drive rated current?

Select drive with a higher rating.

Did a sudden load increase
occur or is the motor blocked?

Avoid sudden overloads.
Possibly use drive and motor with
higher rating.

Overcurrent

during running

Are the motor terminals U/T1,
V/T2, W/T3 short-circuited?

Check motor lines and the motor for a
short circuit.

Is the deceleration time setting
too short?

Set a longer deceleration time.



during deceleration

Are the motor terminals U/T1,
V/T2, W/T3 short-circuited?

Check motor lines and the motor for a
short circuit

Is the acceleration time setting
too short?

Increase the acceleration time

Are the motor terminals short-
circuited?

Check motor lines and the motor for a
short circuit

Is the manual boost (parameter

A42

) set too high?

Reduce the boost under parameter

A42


during acceleration

Is the motor blocked?

Check the motor load or breakaway
torque


at a standstill

Is there an earth fault at the
output terminals or at the motor?

Check the output lines or the motor for
an earth fault



Triggering of internal
motor protection

The internal electronic motor
protection has been triggered
due to overloading of the
connected motor.

Use a motor and converter with a
higher rating

Check the entry under parameter

b12

The drive is overloaded The output current is greater

than the drive rated current

Use drive with a higher rating

Set a longer deceleration time.

Inactivate the AVR function for
deceleration (parameter

A81

, enter 01

or 02).

Enter a higher motor voltage under
parameter

A82

.

DC-bus overvoltage

The motor was operated
oversynchronously
(regenerative).

Use the brake chopper.

EEPROM error

Is the temperature too high or is
the drive exposed to electric
noise?

Check the environmental conditions.
Re-enter the programmed
parameters.

E 04

E 05

E 08

E 07

E 03

E 01

E 02